EH Micropilot FMR52 Time-of-Flight Radar for continuos non-contact level measurement in aggressive liquids. DN50 to DN150 Process Connection. 2-wire or 4-wire HART communication. PTFE-filled and flush-mounted horn antenna. FM and CSA approvals.
Approval
AA-Non hazardous area CA-CSA C/US General Purpose CB-CSA C/US IS Cl.I Div.1 Gr.A to D C2-CSA C/US IS Cl.I,II,III Div.1 Gr.A to G, NI Cl.1 Div.2, Ex ia C3-CSA C/US XP Cl.I,II,III Div.1 Gr.A to G, NI Cl.1 Div.2, Ex d FA-FM IS Cl.I Div.1 Gr.A to D FB-FM IS Cl.I,II,III Div.1 Gr.A to G, AEx ia, NI Cl.1 Div.2 FD-FM XP Cl.I,II,III Div.1 Gr.A to G, AEx d, NI Cl.1 Div.2 GR-Non hazardous area + EAC marking 8A-FM/CSA IS+XP Cl.I,II,III Div.1 Gr.A to G 99-Special version, TSP no. to be spec.
(1) Approval for EH FMR52
Power Supply
A-2 wire; 4 to 20mA HART B-2 wire; 4 to 20mA HART, switch output C-2 wire; 4 to 20mA HART + 4 to 20mA analog E-2 wire; FOUNDATION Fieldbus, switch output G-2 to wire; PROFIBUS PA, switch output K-4 wire 90 to 253VAC; 4 to 20mA HART L-4 wire 10.4 to 48VDC; 4 to 20mA HART Y-Special version, TSP no. to be spec.
(2) Power Supply for EH FMR50/52/54/56
Display & Operation
A-W/o, via communication C-SD02 4 line, push buttons + data backup function E-SD03 4 line, illum., touch control + data backup function L-Prepared for display FHX50 + M12 connection M-Prepared for display FHX50 + custom connection Y-Special version, TSP no. to be spec.
(3) Display & Operation for EH FMR50/52/54/56
Housing
A-GT19 Dual compartment, plastic PBT B-GT18 Dual compartment, 316L C-GT20 Dual compartment, Alu, coated Y-Special version, TSP no. to be spec.
(4) Housing for EH FMR52/54/57
Electrical Connection
A-Gland M20, IP66/68 NEMA4X/6P B-Thread M20, IP66/68 NEMA4X/6P C-Thread G1/2, IP66/68 NEMA4X/6P D-Thread NPT1/2, IP66/68 NEMA4X/6P I-Plug M12, IP66/68 NEMA4X/6P M-Plug 7/8", IP66/68 NEMA4X/6P Y-Special version, TSP no. to be spec.
(5) Electrical Connection for EH FMR50/52/54/56
Antenna
BO-Horn 50mm/2", (40)...200oC/(40)...392oF, flush mount BP-Horn 80mm/3", (40)...200oC/(40)...392oF, flush mount YY-Special version, TSP no. to be spec.
(6) Antenna for EH FMR52
Process Connection
CFK-DN50 PN10/16, PTFE>316L flange EN10921 CGK-DN80 PN10/16, PTFE>316L flange EN10921 CHK-DN100 PN10/16, PTFE>316L flange EN10921 CJK-DN150 PN10/16, PTFE>316L flange EN10921 MRK-DIN11851 DN50 PN25 slotted nut, PTFE>316L MTK-DIN11851 DN80 PN25 slotted nut, PTFE>316L TDK-Tri Clamp ISO2852 DN40 to 51 (2"), PTFE>316L, 3A, EHEDG TFK-Tri Clamp ISO2852 DN70 to 76.1 (3"), PTFE>316L, 3A, EHEDG THK-Tri Clamp ISO2852 DN101.6 (4"), PTFE>316L, 3A, EHEDG YYY-Special version, TSP no. to be spec.
(7) Process Connection for EH FMR52